Code | 99111113 | 99111263 | |
Name | TPS/M/D 1500 | TPS/M/D 3000 | |
Power / inrush mode | 1500 / 3000 VA | 3000 / 6000 VA | |
Output | Single phase | Single phase | |
Characteristic | Not isolated | Not isolated | |
VOLTAGE | Range | 150V/300V | 150V/300V |
Accuracy | <0.5% f.s. | <0.5% f.s. | |
Distortion | <0.3% | <0.3% | |
Stability of the output voltage |
<0.1% f.s. | <0.1% f.s. | |
Recovery time of the waveform |
<10ms | <10ms | |
Maximum Compensated drop |
5% s.v. | 5% s.v. | |
Recovery-time of drop on wires |
<200ms | <200ms | |
Output voltage resolution |
0.025% f.s. | 0.025% f.s. | |
SINGLE PHASE (MAX CURRENT) |
RMS continuous (2) 150V |
9.33A | 18.7A |
RMS continuous (2) 300V |
4.67A | 9.3A | |
Inrush Current (3 seconds) (2) 150V |
18.7A | 37.3A | |
Inrush Current (3 seconds) (2) 300V |
9.3A | 18.7A | |
FREQUENCY | Output frequency range | DC (1), 10Hz – 80Hz |
DC (1), 10Hz – 80Hz |
Range of synchronization |
45Hz – 65Hz | 45Hz – 65Hz | |
Frequency resolution | 0.02Hz | 0.02Hz | |
Frequency precision | 100ppm | 100ppm | |
SUPPLY | Input supply | 230Vac ± 10% 1Ph | 230Vac ± 10% 1Ph |
Maximum Input current | 12A | 24A | |
Input Frequency | 50Hz-60Hz | 50Hz-60Hz | |
OTHER | Size (H : W : D) | 191 : 471 : 513 (3) |
191 : 471 : 513 (3) |
Weight | 25Kg | 29Kg | |
Protections | OVP;UVP;OTP | OVP;UVP;OTP | |
Operation Temperature Range |
0-35°C | 0-35°C | |
RS232 | YES | YES | |
RS485 | YES | YES | |
LAN | YES | YES | |
Firmware with SCPI | YES | YES | |
Firmware with MODBUS | YES | YES | |
Remote program |
PS Interface PSM_Interface |
PS Interface PSM_Interface |
|
Driver LabVIEW | PS Driver | PS Driver | |
Manual | 62000447 | 62000447 | |
Protocol Elettrotest |
Elettrotest | Elettrotest | |
Protocol SCPI |
SCPI | SCPI | |
Protocol ModBus |
ModBus | ModBus | |
Datasheet | TPS/M/D 1500 | TPS/M/D 3000 | |
Declaration of conformity | UE UKCA |
||
FILTERS | Single phase | ● | ● |
Not isolated | ● | ● | |
Double range | ● | ● | |
Rack version available | ● | ● | |
OVP = Over voltage protection UVP = Under voltage protection OTP = Over temperature protection f.s. = Full scale (1) Only on 300V range (2) With Resistive load (3) Desk and Rack version |
Code | 99111513 | 99111663 | |
Name | TPS/M/D 6000 | TPS/M/D 9000 | |
Power / inrush mode | 6000 / 12000 VA | 9000 / 18000 VA | |
Output | Single phase | Single phase | |
Characteristic | Not isolated | Not isolated | |
VOLTAGE | Range | 150V/300V | 150V/300V |
Accuracy | <0.5% f.s. | <0.5% f.s. | |
Distortion | <0.3% | <0.3% | |
Stability of the output voltage |
<0.1% f.s. | <0.1% f.s. | |
Recovery time of the waveform |
<10ms | <10ms | |
Maximum Compensated drop |
5% s.v. | 5% s.v. | |
Recovery-time of drop on wires |
<200ms | <200ms | |
Output voltage resolution |
0.025% f.s. | 0.025% f.s. | |
SINGLE PHASE (MAX CURRENT) |
RMS continuous (2) 150V |
38.1A | 60.2A |
RMS continuous (2) 300V |
19.0A | 30.1A | |
Inrush Current (3 seconds) (2) 150V |
84.6A | 123.6A | |
Inrush Current (3 seconds) (2) 300V |
38.1A | 61.8A | |
FREQUENCY | Output frequency range | DC (1), 10Hz – 80Hz |
DC (1), 10Hz – 80Hz |
Range of synchronization |
45Hz – 65Hz | 45Hz – 65Hz | |
Frequency resolution | 0.02Hz | 0.02Hz | |
Frequency precision | 100ppm | 100ppm | |
SUPPLY | Input supply | 400Vac ± 10% 3PH+N | 400Vac ± 10% 3PH+N |
Maximum Input current | 16A/24A neutral | 24A/41A neutral | |
Input Frequency | 50Hz-60Hz | 50Hz-60Hz | |
OTHER | Size (H : W : D) | 281 : 471 : 513 (3) |
281 : 471 : 513 (3) |
Weight | 39Kg | 44Kg | |
Protections | OVP;UVP;OTP | OVP;UVP;OTP | |
Operation Temperature Range |
0-35°C | 0-35°C | |
RS232 | YES | YES | |
RS485 | YES | YES | |
LAN | YES | YES | |
Firmware with SCPI | YES | YES | |
Firmware with MODBUS |
YES | YES | |
Remote program | PS Interface PSM_Interface |
PS Interface PSM_Interface |
|
Driver LabVIEW | PS Driver | PS Driver | |
Manual | 62000447 | 62000447 | |
Protocol Elettrotest |
Elettrotest | Elettrotest | |
Protocol SCPI |
SCPI | SCPI | |
Protocol ModBus |
ModBus | ModBus | |
Datasheet | TPS/M/D 6000 | TPS/M/D 9000 | |
Declaration of conformity | UE UKCA |
||
FILTERS | Single phase | ● | ● |
Not isolated | ● | ● | |
Double range | ● | ● | |
Rack version available | ● | ● | |
OVP = Over voltage protection UVP = Under voltage protection OTP = Over temperature protection f.s. = Full scale (1) Only on 300V range (2) With Resistive load (3) Desk and Rack version |