Cerca
Close this search box.

CPS Trifase

Generatore mono/trifase compatto non isolato e adatto per sistemi di collaudo monofase/trifase.

Scheda tecnica


Zoom image

Zoom image
Code 99110770 99110780
Name CPS 4KVA/8KVA (5KVA) CPS 7,5KVA/15KVA
Power Countinous mode 5KVA 10KVA
Power Inrush mode 4KVA/8KVA 7.5KVA/15KVA
Output 1phase / 3phase 1phase / 3phase
Characteristic Not Isolated Not Isolated
VOLTAGE Range 150V/300V(4) 150V/300V(4)
Accuracy <0.5% f.s. <0.5% f.s.
Distortion <0.6% <0.6%
Stability of the output voltage <0.1% f.s. <0.1% f.s.
Recovery time of the waveform <10ms <10ms
Maximum Compensated drop 5% s.v. 5% s.v.
Recovery-time of drop on wires <200ms. <200ms.
Output voltage resolution 0.025% f.s. 0.025% f.s.
Inrush function
(Max current)
1PH RMS continuous (2) 150V 26,7 A 50 A
RMS continuous (2) 300V 13,3 A 25 A
Inrush Current (3 seconds)(2) 150V 53,4 A 100 A
Inrush Current (3 seconds)(2) 300V 26,6 A 50 A
3PH RMS continuous (2) 150V 8,9 A 16,7 A
RMS continuous (2) 300V 4,4 A 8,3 A
Inrush Current (3 seconds)(2) 150V 17,8 A 33,4 A
Inrush Current (3 seconds)(2) 300V 8,8 A 16,6 A
Countinous function
(Max current)
1PH RMS continuous (2) 150V 33,2 A 66,4 A
RMS continuous (2) 300V 16,6 A 33,2 A
3PH RMS continuous (2) 150V 11,1 A 22,2 A
RMS continuous (2) 300V 5,5 A 11,1 A
FREQUENCY Output frequency range 10Hz(5) – 80Hz 10Hz(5) – 80Hz
Range of synchronization 45Hz – 65Hz 45Hz – 65Hz
Frequency resolution 0.02Hz 0.02Hz
Frequency precision 100ppm 100ppm
SUPPLY Input supply 400Vac ± 10% 3PH+N 400Vac ± 10% 3PH+N
Maximum Input current 12A/24A neutral 18A/41A neutral
Input Frequency 47Hz-63Hz 47Hz-63Hz
OTHER Size (H : W : D) 281 : 471 : 513 1150 :585 : 600
Weight 54Kg 180Kg
Protections OVP;UVP;OTP OVP;UVP;OTP
Operation Temperature Range 0-35°C 0-35°C
RS232 YES YES
RS485 OPTION OPTION
LAN OPTION OPTION
Remote program PS Interface
PSM_Interface
PS Interface
PSM_Interface
Driver LabVIEW PS Driver PS Driver
Manual 62000585_it_en 
CPS Parameters
62000585_it_en 
CPS Parameters
Brochure CPS 5 KVA CPS 10 KVA
Communication protocol
manuals
Elettrotest
SCPI
Elettrotest
SCPI
Declaration of conformity UE
UKCA
UE
UKCA
FILTER Single/Three phase
Not isolated
Double range
Rack version available
OVP = Over voltage protection
UVP = Under voltage protection
OTP = Over temperature protection
f.s. = Full scale
(2) With Resistive load
(4) Other range on request
(5) It is possible on remote interface to set 10Hz but you must
decrease the maximum voltage

Zoom image

Zoom image
Code 99110790 99110800
Name CPS 15KVA/30KVA (20KVA) CPS 30KVA/60KVA (40KVA)
Power Countinous mode 20KVA 40KVA
Power Inrush mode 15KVA/30KVA 30KVA/60KVA
Output 1phase / 3phase 1phase / 3phase
Characteristic Not Isolated Not Isolated
VOLTAGE Range 150V/300V(4) 150V/300V(4)
Accuracy <0.5% f.s. <0.5% f.s.
Distortion <0.6% <0.6%
Stability of the output voltage <0.1% f.s. <0.1% f.s.
Recovery time of the waveform <10ms <10ms
Maximum Compensated drop 5% s.v. 5% s.v.
Recovery-time of drop on wires <200ms. <200ms.
Output voltage resolution 0.025% f.s. 0.025% f.s.
Inrush function
(Max current)
1PH RMS continuous (2) 150V 100 A 200 A
RMS continuous (2) 300V 50 A 100 A
Inrush Current (3 seconds)(2) 150V 200 A 400 A
Inrush Current (3 seconds)(2) 300V 100 A 200 A
3PH RMS continuous (2) 150V 33,4 A 66,8 A
RMS continuous (2) 300V 16,7 A 33,4 A
Inrush Current (3 seconds)(2) 150V 66,8 A 134 A
Inrush Current (3 seconds)(2) 300V 33,4 A 66,8 A
Countinous function
(Max current)
1PH RMS continuous (2) 150V 133 A 266 A
RMS continuous (2) 300V 66,4 A 133 A
3PH RMS continuous (2) 150V 44,4 A 88,9 A
RMS continuous (2) 300V 22 A 44 A
FREQUENCY Output frequency range 10Hz(5) – 80Hz 10Hz(5) – 80Hz
Range of synchronization 45Hz – 65Hz 45Hz – 65Hz
Frequency resolution 0.02Hz 0.02Hz
Frequency precision 100ppm 100ppm
SUPPLY Input supply 400Vac ± 10% 3PH+N 400Vac ± 10% 3PH+N
Maximum Input current 34A/64A neutral 60A/125A neutral
Input Frequency 47Hz-63Hz 47Hz-63Hz
OTHER Size (H : W : D) 1410 :585 : 600 1410 :585 : 600
Weight 300Kg 450Kg
Protections OVP;UVP;OTP OVP;UVP;OTP
Operation Temperature Range 0-35°C 0-35°C
RS232 YES YES
RS485 OPTION OPTION
LAN OPTION OPTION
Remote program PS Interface
PSM_Interface
PS Interface
PSM_Interface
Driver Labview PS Driver PS Driver
Manual 62000585_it_en
CPS Parameters
62000585_it_en 
CPS Parameters
Brochure CPS 20 KVA CPS 40 KVA
Communication protocol
manuals
Elettrotest
SCPI
Elettrotest
SCPI
Declaration of conformity UE
UKCA
UE
UKCA
FILTER Single/Three phase
Not isolated
Double range
Rack version available
OVP = Over voltage protection
UVP = Under voltage protection
OTP = Over temperature protection
f.s. = Full scale
(2) With Resistive load
(4) Other range on request
(5) It is possible on remote interface to set 10Hz but you must
decrease the maximum voltage