Generatore mono/trifase isolato e adatto per carichi molto distorcenti mantenendo una tensione pura, precisa e stabile.

Scheda tecnica


Zoom image

Zoom image

Zoom image

Zoom image
Code 99110547 99110557 99110585
Name TPS/T 7.5K22.5S (10K) TPS/T 15K45S (20K) TPS/T 30K60S (40K)
Power Continous mode 10 KVA 20 KVA 40 KVA
Power Inrush mode 7.5 KVA/22.5 KVA 15 KVA/45 KVA 30 KVA / 60 KVA
Output 1phase / 3phase 1phase / 3phase 1phase / 3phase
Characteristic Isolated Isolated Isolated
VOLTAGE Range 150V/300V(4) 150V/300V(4) 150V/300V(4)
Accuracy <0.5% f.s. <0.5% f.s. <0.5% f.s.
Distortion <0.3% <0.3% <0.3%
Stability of the output voltage <0.1% f.s. <0.1% f.s. <0.1% f.s.
Recovery time of the waveform <10ms <10ms <10ms
Maximum Compensated drop 5% s.v. 5% s.v. 5% s.v.
Recovery-time of drop on wires <200ms <200ms <200ms
Output voltage resolution 0.025% f.s. 0.025% f.s. 0.025% f.s.
INRUSH FUNCTION
(MAX CURRENT)
1PH RMS continuous (2) 150V 49.6A 100A 200A
RMS continuous (2) 300V 24.8A 50A 100A
Inrush Current (3 seconds)(2) 150V 149A 300A 400A
Inrush Current (3 seconds)(2) 300V 74.4A 150A 200A
3PH RMS continuous (2) 150V 16.6A 33.3A 66.6A
RMS continuous (2) 300V 8.33A 16.7A 33.3A
Inrush Current (3 seconds)(2) 150V 33.2A 100A 133A
Inrush Current (3 seconds)(2) 300V 16.33A 50A 66.7A
CONTINUOUS FUNCTION
(MAX CURRENT)
1PH RMS continuous (2) 150V 66.7A 133A 267A
RMS continuous (2) 300V 33.3A 66.5A 133A
3PH RMS continuous (2) 150V 22.2A 44.4A 88.9A
RMS continuous (2) 300V 11.1A 22.2A 44.5A
FREQUENCY Output frequency range 40Hz(5) – 80Hz 40Hz(5) – 80Hz 40Hz(5) – 80Hz
Range of synchronization 45Hz – 65Hz 45Hz – 65Hz 45Hz – 65Hz
Frequency resolution 0.02Hz 0.02Hz 0.02Hz
Frequency precision 100ppm 100ppm 100ppm
SUPPLY Input supply 400Vac ± 10% 3Ph Without neutral 400Vac ± 10% 3Ph Without neutral 400Vac ± 10% 3Ph Without neutral
Maximum Input current 20A 70A 120A
Input Frequency 47Hz-63Hz 47Hz-63Hz 47Hz-63Hz
OTHER Size (H : W : D) 1670 : 620 : 625 1670 : 920 : 625 1670 : 920 : 625
Weight 200Kg 400Kg 600Kg
Protections OVP; UVP; OTP OVP; UVP; OTP OVP; UVP; OTP
Operation Temperature Range 0-35°C 0-35°C 0-35°C
RS232 YES YES YES
RS485 OPTION OPTION OPTION
LAN OPTION OPTION OPTION
Remote program PS Interface
PSM_Interface
PS Interface
PSM_Interface
PS Interface
PSM_Interface
Driver LabVIEW PS Driver PS Driver PS Driver
Manual 62000560_it_en 
TPS Parameters
62000560_it_en 
TPS Parameters
62000560_it_en 
TPS Parameters
Brochure TPS_10K TPS_20K TPS_40K
Communication protocol
manuals
Elettrotest
SCPI
Elettrotest
SCPI
Elettrotest
SCPI
Declaration of conformity UE
UKCA
FILTERS Single phase
Three phase
Single/Three phase
Isolated
Double range
OVP = Over voltage protection
UVP = Under voltage protection
OTP = Over temperature protection
f.s. = Full scale
(1) Only on 300V range
(2) With Resistive load
(3) Desk and Rack version
(4) Other range on request
(5) It is possible on remote interface to set 10Hz but you must
decrease the maximum voltage
(6) It is possible to use in single phase mode but with 1/3 of nominal
power. It is possible asymmetrical output current

Zoom image

Zoom image

Zoom image

Zoom image
Code 99110540 99116523 99110600
Name TPS/T 60K TPS/T 50K 120S (60K) TPS/T 90K
Power Continous mode 72 KVA 72KVA 95 KVA
Power Inrush mode 50 KVA/ 120 KVA
Output 1phase / 3phase 1phase / 3phase 3phase(6)
Characteristic Isolated Isolated Isolated
VOLTAGE Range 150V/300V(4) 150V/300V(4) 150V/300V(4)
Accuracy <0.5% <0.5% <0.5%
Distortion <0.3% <0.3% <0.3%
Stability of the output voltage <0.1% <0.1% <0.1%
Recovery time of the waveform <10ms <10ms <10ms
Maximum Compensated drop 5% f.s 5% f.s 5% f.s
Recovery-time of drop on wires <200ms <200ms <200ms
Output voltage resolution 0.025% f.s. 0.025% f.s. 0.025% f.s.
INRUSH FUNCTION
(MAX CURRENT)
1PH RMS continuous (2) 150V 340A
RMS continuous (2) 300V 170A
Inrush Current (3 seconds)(2) 150V 960A
Inrush Current (3 seconds)(2) 300V 480A
3PH RMS continuous (2) 150V 56A
RMS continuous (2) 300V 112A
Inrush Current (3 seconds)(2) 150V 320A
Inrush Current (3 seconds)(2) 300V 160A
CONTINUOUS FUNCTION
(MAX CURRENT)
1PH RMS continuous (2) 150V 480A 480A
RMS continuous (2) 300V 240A 240A
3PH RMS continuous (2) 150V 160A 160A 213A
RMS continuous (2) 300V 80A 80A 107A
FREQUENCY Output frequency range 40Hz(5) – 80Hz 40Hz(5) – 80Hz 40Hz(5) – 80Hz
Range of synchronization 45Hz – 65Hz 45Hz – 65Hz 45Hz – 65Hz
Frequency resolution 0.02Hz 0.02Hz 0.02Hz
Frequency precision 100ppm 100ppm 100ppm
SUPPLY Input supply 400Vac ± 10% 3Ph Without neutral 400Vac ± 10% 3Ph Without neutral 400Vac ± 10% 3Ph Without neutral
Maximum Input current 160A 250A 250A
Input Frequency 47Hz-63Hz 47Hz-63Hz 47Hz-63Hz
OTHER Size (H : W : D) 1800 :1200 : 800 1800 :1200 : 800 1800 :1200 : 1000
Weight 960Kg 1060Kg 1200Kg
Protections OVP;UVP;OTP OVP;UVP;OTP OVP;UVP;OTP
Operation Temperature Range 0-35°C 0-35°C 0-35°C
RS232 YES YES YES
RS485 OPTION OPTION OPTION
LAN OPTION OPTION OPTION
Remote program PS Interface
PSM_Interface
PS Interface
PSM_Interface
PS Interface
PSM_Interface
Driver LabVIEW PS Driver PS Driver PS Driver
Manual 62000560_it_en 
TPS Parameters
62000560_it_en 
TPS Parameters
62000560_it_en 
TPS Parameters
Brochure TPS_60K TPS 60K-50K120S TPS_90K
Communication protocol
manuals
Elettrotest
SCPI
Elettrotest
SCPI
Elettrotest
SCPI
Declaration of conformity UE
UKCA
FILTERS Single phase
Three phase
Single/Three phase
Isolated
Double range
OVP = Over voltage protection
UVP = Under voltage protection
OTP = Over temperature protection
f.s. = Full scale
(1) Only on 300V range
(2) With Resistive load
(3) Desk and Rack version
(4) Other range on request
(5) It is possible on remote interface to set 10Hz but you must
decrease the maximum voltage
(6) It is possible to use in single phase mode but with 1/3 of nominal
power. It is possible asymmetrical output current

Vuoi essere aggiornato sui nostri prodotti?
Iscriviti alla newsletter.