Series of three-phase Wattmeters with precision classes of 1%, 0.5% 0.3% and 0.04%, and a band of frequency from 40Hz from 400Hz and from DC to 2MHz. The Wattmeter series are available in table, rack, box and Aron three-phase versions.

Scheda tecnica


Zoom image


Zoom image

Zoom image

Zoom image
Code 99100012/13 99100101 99997355
Name WATTMETRO TRIFASE PORTATILE WATTMETRO TRIFASE DA RACK CON TA E TV EXT VIW INTERFACE 3N HIGH PRECISION
V in (V) 115/230 V ± 10% – 50÷60 Hz 110/220V±10%; 50÷60Hz 90/265V RMS 50÷60Hz; 35 VA MAX
V Range (Vrms full scale) 150, 300, 600 20, 40, 80, 200, 400, 800 1Vpk to 3000Vpk (1000Vrms) in 8 ranges
20% over-range ability maintains 300Vpk range with 240Vrms
I Range (Arms full scale) (1) 2, 5, 10, 20, 50 2, 5, 10, 20, 50 100mApk to 300Apk (30Arms) in 8 ranges
Power Range (W) Single-phase connectors 0.3÷30 kW

(30÷3000 W)

Three-phase connectors 0.52÷52 kW

(52÷5200 W)

40 W÷40 kW ~0,1W ÷ 30 kW
Precision ± 0.3% Full Scale ± 0.3% Full Scale Voltage Accuracy: 0.04% Rdg + 0.04% Rng + (0.004% x kHz) + 1mV (2)
Current Accuracy: 0.04% Rdg + 0.04% Rng + (0.004% x kHz) + 100uA (2)
Phase Accuracy: 0.04% Rdg + 0.04% Rng + (0.004% x kHz) + 1mV (2)
10 millidegrees + (20 millidegrees x kHz) (50Arms shunt)
Watts Accuracy: [0.05% + 0.03%/pf +(0.01% x kHz)/pf] Rdg + 0.05%VA Rng
DC Accuracy:
Voltage – 0.1% Rdg + 0.1% Rng + 10mV (or 10uV external)
Current – 0.1% Rdg + 0.1% Rng + 1mA (or 10uV external)
Insulation 3 kV rms for 60 sec. ‘2000Vac, 60 sec. Fully Isolated 1000V Cat II
Manual 62000230 62000310 User Manual: 62000212
Communication Manual: 62000213
Brochure VIW INTERFACE-T VIW EURO ARON TA-TV EXT Brochure VIV Interface 1N – 3N
Accessories 62000000

62000010

62000020

62000390

62000000

62000010

62000020

62000390

62000400

F
i
l
t
e
r
s
R
a
n
g
e
Single-phase
Three-phase
S
t
r
u
c
t
u
r
e
PCB
Rack
Desk-top