Isolated three-phase generator, suitable for high-power systems with high pickup.

Data sheet


Zoom image

Zoom image
Code 99116553 99116803
Name HPS 60KVA/ 90KVA HPS 100KVA
Power Countinous mode 100KVA
Power Inrush mode 60KVA/90KVA
Output 3phase(6) 3phase(6)
Characteristic Isolated Isolated
VOLTAGE Range 150V/300V(4) 150V/300V(4)
Accuracy <0.5% f.s. <0.5% f.s.
Distortion <0.6% <0.6%
Stability of the output voltage <0.1% f.s. <0.1% f.s.
Recovery time of the waveform <10ms <10ms
Maximum Compensated drop 5% s.v. 5% s.v.
Recovery-time of drop on wires <200ms. <200ms.
Output voltage resolution 0.025% f.s. 0.025% f.s.
Inrush function
(Max current)
1PH RMS continuous (2) 150V 134 A
RMS continuous (2) 300V 67 A
Inrush Current (3 seconds)(2) 150V 196 A
Inrush Current (3 seconds)(2) 300V 98 A
3PH RMS continuous (2) 150V 134 A
RMS continuous (2) 300V 67 A
Inrush Current (3 seconds)(2) 150V 196 A
Inrush Current (3 seconds)(2) 300V 98 A
Countinous function
(Max current)
1PH RMS continuous (2) 150V 228 A
RMS continuous (2) 300V 114 A
3PH RMS continuous (2) 150V 228 A
RMS continuous (2) 300V 114 A
FREQUENCY Output frequency range 50Hz(5) – 80Hz 50Hz(5) – 80Hz
Range of synchronization 45Hz – 65Hz 45Hz – 65Hz
Frequency resolution 0.02Hz 0.02Hz
Frequency precision 100ppm 100ppm
SUPPLY Input supply 400Vac±10% 3PH 400Vac±10% 3PH
Maximum Input current 150A 250A
Input Frequency 47Hz-63Hz 47Hz-63Hz
OTHER Size (H : W : D) 1670 : 920 : 825 1670 : 920 : 825
Weight 550 Kg 800 kg
Protections OVP,UVP;OTP OVP,UVP;OTP
Operation Temperature Range 0-35°C 0-35°C
RS232 YES YES
RS485 OPTION OPTION
LAN OPTION OPTION
Remote program PS Interface
PSM_Interface
PS Interface
PSM_Interface
Driver LabVIEW PS Driver PS Driver
Manual 62000590_it_en
TPS Parameters
62000590_it_en
TPS Parameters
Brochure HPS 60KVA HPS 100KVA
Communication protocol
manuals
Elettrotest
SCPI
Elettrotest
SCPI
Declaration of conformity UE
UKCA
UE
UKCA
FILTERS Three phase
Isolated
Double range
OVP = Over voltage protection
UVP = Under voltage protection
OTP = Over temperature protectionf.s. = Full scale
(2) With Resistive load
(3) Desk and Rack version
(5) It is possible on remote interface to set 10Hz but you must
decrease the maximum voltage
(6) It is possible to use in single phase mode but with 1/3 of nominal
power. It is possible asymmetrical output current

Zoom image

Zoom image

Zoom image
Code 99116823 99116953 99116963
Name HPS 60KVA/180KVA (100KVA) HPS 120KVA/360KVA (200KVA) HPS 200KVA PARALLEL
Power Countinous mode 100KVA 200KVA 200KVA
Power Inrush mode 60KVA/180KVA(6) 120KVA/360KVA(6) 120KVA/360KVA(6)
Output 3phase(6) 3phase(6) 3phase(6)
Characteristic Isolated Isolated Isolated
VOLTAGE Range 150V/300V(4) 150V/300V(4) 150V/300V(4)
Accuracy <0.5% f.s. <0.5% f.s. <0.5% f.s.
Distortion <0.6% <0.6% <0.6%
Stability of the output voltage <0.1% f.s. <0.1% f.s. <0.1% f.s.
Recovery time of the waveform <10ms <10ms <10ms
Maximum Compensated drop 5% s.v. 5% s.v. 5% s.v.
Recovery-time of drop on wires <200ms. <200ms. <200ms.
Output voltage resolution 0.025% f.s. 0.025% f.s. 0.025% f.s.
Inrush function
(Max current)
1PH RMS continuous (2) 150V 137 A 279 A 279 A
RMS continuous (2) 300V 68 A 137 A 137 A
Inrush Current (3 seconds)(2) 150V 410 A 837 A 837 A
Inrush Current (3 seconds)(2) 300V 205 A 410 A 410 A
3PH RMS continuous (2) 150V 137 A 279 A 279 A
RMS continuous (2) 300V 68 A 137 A 137 A
Inrush Current (3 seconds)(2) 150V 410 A 837 A 837 A
Inrush Current (3 seconds)(2) 300V 205 A 410 A 410 A
Countinous function
(Max current)
1PH RMS continuous (2) 150V 228 A 465 A 465 A
RMS continuous (2) 300V 114 A 228 A 228 A
3PH RMS continuous (2) 150V 228 A 465 A 465 A
RMS continuous (2) 300V 114 A 228 A 228 A
FREQUENCY Output frequency range 50Hz(5) – 80Hz 50Hz(5) – 80Hz 50Hz(5) – 80Hz
Range of synchronization 45Hz – 65Hz 45Hz – 65Hz 45Hz – 65Hz
Frequency resolution 0.02Hz 0.02Hz 0.02Hz
Frequency precision 100ppm 100ppm 100ppm
SUPPLY Input supply 400Vac±10% 3PH 400Vac±10% 3PH 400Vac±10% 3PH
Maximum Input current 250A 500A 500A
Input Frequency 47Hz-63Hz 47Hz-63Hz 47Hz-63Hz
OTHER Size (H : W : D) 1670 : 920 : 825 1800 :1200 : 1000 1800 :1200 : 1000
Weight 800 kg 1400 Kg 1600 Kg
Protections OVP,UVP;OTP OVP,UVP;OTP OVP,UVP;OTP
Operation Temperature Range 0-35°C 0-35°C 0-35°C
RS232 YES YES YES
RS485 OPTION OPTION OPTION
LAN OPTION OPTION OPTION
Remote program PS Interface
PSM_Interface
PS Interface
PSM_Interface
PS Interface
PSM_Interface
Driver LabVIEW PS Driver PS Driver PS Driver
Manual 62000590_it_en
TPS Parameters
62000590_it_en
TPS Parameters
62000591_it_en
TPS Parameters
Brochure HPS 100KVA HPS 200KVA HPS 200KVA
Communication protocol
manuals
Elettrotest
SCPI
Elettrotest
SCPI
Elettrotest
SCPI
Declaration of conformity UE
UKCA
UE
UKCA
UE
UKCA
FILTERS Three phase
Isolated
Double range
OVP = Over voltage protection
UVP = Under voltage protection
OTP = Over temperature protectionf.s. = Full scale
(2) With Resistive load
(3) Desk and Rack version
(5) It is possible on remote interface to set 10Hz but you must
decrease the maximum voltage
(6) It is possible to use in single phase mode but with 1/3 of nominal
power. It is possible asymmetrical output current